failure to Start Some Devices on Load

Some high capacitance loads like Compact fluorescent Lamp (CfL) or Switched Mode
Power Supply (SMPS) will shut down the inverter under overload condition if the inverter
is switched oN with these loads in oN condition. However, if these loads are switched
off first and switched oN only after around 10 sec after the inverter is switched oN (as
already recommended under switching oN procedure), the inverter may not shut down.
Hence, do not switch oN the inverter with such loads in oN condition.

monitoring of operational Status & protections

Normal / abnormal behavior can be monitored by observing Green LeD (5, Power), Yellow
LeD (6, Input fault), red LeD (4, fault) and buzzer. Details are given in Table 6.1 below:

table 6.1 protections and monitoring

operating

condition/

protection

threshold/

reason

Green

LeD (5,

power)

yeLLoW

LeD (6,

input

fault)

reD

LeD (4,

fault)

Buzzer

remedy/reset

Normal

-

ON

OFF

OFF

OFF

-

Low DC Input

Alarm

10.8V ± 0.3V

ON

OFF

OFF

ON

Check battery voltage and

input voltage drop.

Auto reset when voltage

> 10.5 V ± 0.3V.

No Output

due to Low DC

Input Voltage

shutdown

10.5V ± 0.3V

OFF

ON

OFF

OFF

Check battery voltage and

input voltage drop.

Auto reset when voltage rises

to >11.5V.

No output due

to High DC

Input Voltage

Shut Down

15.5 ± 0.2V

OFF

ON

OFF

OFF

Check charger voltage.

Auto reset when voltage

< 15.5V.

No Output

due to High

Temperature

Shut Down

Internal hot

spot > 88°C

to 115°C

OFF

ON

OFF

OFF

Check ambient temperature,

fan and loss of cool

replacement air .

Auto reset when hot spot

cools down 10°C to 15°C

below the threshold.

SECTION 6 |

Protections Monitoring

& Troubleshooting