4.

Mount the connected assembly onto the floor plate, and secure

it using (2) #1/4 x 20 x 1" screws (supplied).

Armature Assembly Mounting

NOTE: Armature assembly must be mounted vertically (Figure

5) to obtain correct alignment with the electromagnet.

120V AC 24V AC/

DC

COM

FRONT

VIEW

TOP

VIEW

Figure 4. Terminal Block

Figure 6. Thru-Bolt Mounting

Figure 7. Surface Concealed Mounting

Figure 5. Armature Mounting

P/N 3100536 ISSUE 1
501-152300-0-01

Mounting holes

Armature

(base view)

1.

Using a 5/32" Allen wrench, turn the contact plate adjusting screw

(Figures 6 and 7) counterclockwise to loosen the contact plate.

2.

Place the transfer marking points in the armature mounting holes

(Figure 5).

Mounting holes

Armature

(base view)

3.

To locate the two mounting holes in the door, hold the contact

plate centered against the magnet, open the door and press

against the transfer marking points on the armature base.

4.

Mount the armature assembly using one of the following methods:

a.

Thru-bolt mounting (Figure 6). Center punch the two holes

(at the points marked in step 3) and drill 5/16" diameter

through the door. Distance between the center points should

equal 1 3/4" (44 mm).

NOTE: Thru-bolt mounting is recommended for standard 1 3/4"

(44 mm) hollow metal, hollow core or composite type

wood doors.

Secure the armature assembly, with the contact plate adjust

screw facing up, to the door as shown in Figure 6 using

(2) #1/4-20 x 2" screws (supplied)

NOTE: For 2" doors, use (2) 1/4-20 x 2-1/4" bolts.

b. Surface concealed mounting (Figure 7). Measure two

points for 1/8" holes drilled 1/2" on center equidistant from

each marked point. Center punch the holes and drill 1/8"

diameter x 1 1/4" deep. Install the concealed mounting plate

using the two #10 x 1 1/2" screws provided.

NOTE: Surface concealed mounting is not recommended for

hollow metal, hollow core, or composite type wood

doors.

Align the holes for the concealed mounting plate in the

armature base with the pins on the concealed mounting plate.

Secure the armature assembly, with the contact plate adjust

screw facing up as shown in Figure 7, to the door by

tightening the set screw.

5.

Align the contact plate against the electromagnet. The contact

plate must be centered and lie flat against the magnet to ensure

sufficient holding force. Tighten the contact plate adjusting screw

until the plate is firm but not set. Do not overtighten the contact

plate.

6.

Recheck alignment and adjust if necessary.

7.

Adjust the door closer to exert 3 pounds of force when the door

is open and armature and magnet are in contact.

8.

Energize the electromagnet and check operation.

Holes for
concealed
mounting
plate

Armature

(base view)

2 Transfer points

PAGE 2

Lock edge
of door

2 3/8"

(60 mm)

5 5/8" (143 mm)

approx.

2"

(51 mm)

1 11/16"
(43 mm)

floor line

1 3/4"

(44 mm)

Door Plate

1 5/8"

(41 mm)

DOOR

(2) #1/4-20 x 2"

(51 mm)

screws provided

for a standard

1 3/4" (44 mm)

door

2" (51 mm) from floor to center

Contact plate

adjusting screw

Concealed
mounting
plate

1/2"

(13 mm)

Two #10 x 1 1/2"

(38 mm) screws

(supplied)

Set screw.
Tighten with 6/32" Allen wrench
to secure armature onto
mounting plate.

Door

Contact plate

Contact plate
adjusting screw

1/2" (13 mm)

Advertising