Wiring, Testing, Specifications – Edwards Signaling SA-DACT Dialer Manuel d'utilisation

Page 2

Advertising
background image

2 / 8

P/N 3101099 • REV 03 • REB 25JAN13

Wiring

The dialer phone lines connect to connectors on the dialer's
main circuit board. Phone line 1 connects to connector J1 and
phone line 2 connects to connector J4.

The card typically connects to an RJ-31X block using an
8-position, 4-conductor modular cord. Wire the RJ-31X block
as shown below.

Note:

Install a listed secondary telephone protector between

the telco network and the SA-DACT card. The SA-DACT card
must be the next piece of equipment that connects to the
telephone company (TELCO) telephone lines.

Figure 3: SA-DACT wiring

Tip

Ring

Tip

Ring

Tip

Ring

Tip

Ring

Protected premises

punch down block

TELCO

Line 2

TELCO

Line 1

PBX

RJ-31X block

(supplied by installer)

8-position, 4-conductor
modular cords
(supplied by installer)

LINE 2

2

3

4

5

7

6

8

1

LINE 1

2

3

4

5

7

6

8

1

J1

J4

Telephone protector

Telephone protector

Testing

A dialer test is a test of the telephone line for each dialer
account. When a dialer is tested, a normal or abnormal test
message (depending on the state of the system) is sent to the
selected account. If the dialer is set up for dual line operation,
a test message is sent to both lines regardless of the success
of the transmission for either account.

Note:

Before conducting a test, configure the dialer’s accounts

for proper operation.

To conduct a dialer test:

1. Press the control panel's Menu button.

2. Choose Test.

3. Choose Dialer.

4. Select the account that you want to test.

5. Press Enter.

Note:

The test message is sent to the CMS account that

you selected. For verification of the CMS account
receiving the test message, you must be in contact with
the CMS account during the test. Nothing is displayed on
the LCD display.

6. Press Cancel to return to the previous menu.

– or –

Press the Menu button to exit menu mode.

Specifications

Phone line type

One or two loop-start lines on a public,
switched network

Phone line connector

RJ-31/38X (C31/38X)

Communication formats

Contact ID (SIA DC-05)

Operating voltage

24 VDC

Operating current

Standby/Alarm: 41 mA
Max.: 100 mA

FCC registration number

GESAL01BSADACT

Industry Canada
Registration number

3944A-SADACT

Ringer equivalence
number

0.1B

Operating environment

Temperature

Humidity

32 to 120°F (0 to 49°C)
0 to 93% RH, noncondensing at 90°F
(32°C)