Wiring, Testing, Specifications – Edwards Signaling SA-DACT Dialer Manuel d'utilisation
Page 2

2 / 8
P/N 3101099 • REV 03 • REB 25JAN13
Wiring
The dialer phone lines connect to connectors on the dialer's
main circuit board. Phone line 1 connects to connector J1 and
phone line 2 connects to connector J4.
The card typically connects to an RJ-31X block using an
8-position, 4-conductor modular cord. Wire the RJ-31X block
as shown below.
Note:
Install a listed secondary telephone protector between
the telco network and the SA-DACT card. The SA-DACT card
must be the next piece of equipment that connects to the
telephone company (TELCO) telephone lines.
Figure 3: SA-DACT wiring
Tip
Ring
Tip
Ring
Tip
Ring
Tip
Ring
Protected premises
punch down block
TELCO
Line 2
TELCO
Line 1
PBX
RJ-31X block
(supplied by installer)
8-position, 4-conductor
modular cords
(supplied by installer)
LINE 2
2
3
4
5
7
6
8
1
LINE 1
2
3
4
5
7
6
8
1
J1
J4
Telephone protector
Telephone protector
Testing
A dialer test is a test of the telephone line for each dialer
account. When a dialer is tested, a normal or abnormal test
message (depending on the state of the system) is sent to the
selected account. If the dialer is set up for dual line operation,
a test message is sent to both lines regardless of the success
of the transmission for either account.
Note:
Before conducting a test, configure the dialer’s accounts
for proper operation.
To conduct a dialer test:
1. Press the control panel's Menu button.
2. Choose Test.
3. Choose Dialer.
4. Select the account that you want to test.
5. Press Enter.
Note:
The test message is sent to the CMS account that
you selected. For verification of the CMS account
receiving the test message, you must be in contact with
the CMS account during the test. Nothing is displayed on
the LCD display.
6. Press Cancel to return to the previous menu.
– or –
Press the Menu button to exit menu mode.
Specifications
Phone line type
One or two loop-start lines on a public,
switched network
Phone line connector
RJ-31/38X (C31/38X)
Communication formats
Contact ID (SIA DC-05)
Operating voltage
24 VDC
Operating current
Standby/Alarm: 41 mA
Max.: 100 mA
FCC registration number
GESAL01BSADACT
Industry Canada
Registration number
3944A-SADACT
Ringer equivalence
number
0.1B
Operating environment
Temperature
Humidity
32 to 120°F (0 to 49°C)
0 to 93% RH, noncondensing at 90°F
(32°C)