Figure 2: Base installation option 2

1

3

4

5

2

6

2

1.

4 in. square electrical box

2.

Adaptor bracket

3.

B4U base assembly

4

Screws

5.

Trim ring

6.

Aligning arrows

Wiring

Wire in accordance with NFPA 72 or CAN/ULC-S524. Be sure
to observe the polarity of the terminals on the terminal block as
shown in the diagram.

Break the wire run at each terminal. Do not loop signaling
circuit field wires around terminals.

Caution:

To avoid accidental damage to the panel, disconnect

all power before wiring the unit.

Note:

If shielded cable is used, the following recommendations

apply:

Shielded wire is required only in environments with very
high electrical noise.

Use of shield connections must be continuous and must
be insulated from ground. Electrical tape is recommended
as a minimum to insulate the shield.

For Class B wiring, all shields must be continuous and
insulated from ground, except at the originating panel.

Figure 3: Base wiring (option 2 installation shown)

1

3

2

4

5

6

1

2

5

1.

From previous device or controller

2.

Optional trim ring

3.

Optional bracket

4.

Maximum resistance per wire must not exce

ed 10 Ω

5.

To next device

Terminal

Description

Terminal Description

1

SLC in + and
SLC out (+)

4

Not used

2

SLC in −

5

Remote LED +

3

Not used

6

Remote LED −

and SLC out −

Specifications

Base diameter

Without trim ring

With trim ring


4.35 in. (110.49 mm)
6.0 in. (152 mm)

Height from box (including
detector)

2.08 in. (53 mm)

Maximum distance

Ceiling


Wall


Not less than 4 in. (100 mm) from the
sidewall
Between 4 and 12 in. (100 and
300 mm) from the ceiling

Wire size

12 to 18 AWG wire (0.75 to 2.5 mm²)

Compatible detectors

FX-PD, E-PD, FX-PHD, E-PHD,
FX-HD, E-HD, V-PS, V-PHS, V-HRD,
and V-HFD

Compatible electrical boxes

4 × 4 in. octagonal ring (mud box)

1-7/8 in. (47 mm) deep single-gang
box

4 in. square x 2-1/2 in. (64 mm) deep
box (requires using the included
adaptor bracket and trim ring)

Operating environment

Temperature
Relative humidity


32 to 120°F (0 to 49°C)
0 to 93% noncondensing

Storage temperature range

−4 to 140°F (−20 to 60°C)