Wiring
Wire in accordance with NFPA 72 or CAN/ULC-S524. Be sure
to observe the polarity of the terminals on the terminal block as
shown in the diagram.
Break the wire run at each terminal. Do not loop signaling
circuit field wires around terminals.
Caution:
To avoid accidental damage to the panel, disconnect
all power before wiring the unit.
Note:
If shielded cable is used, the following recommendations
apply:
•
Shielded wire is required only in environments with very
high electrical noise.
•
Use of shield connections must be continuous and must
be insulated from ground. Electrical tape is recommended
as a minimum to insulate the shield.
•
For Class B wiring, all shields must be continuous and
insulated from ground, except at the originating panel.
Figure 3: Base wiring (option 2 installation shown)
1
3
2
4
5
6
1
2
5
1.
From previous device or controller
2.
Optional trim ring
3.
Optional bracket
4.
Maximum resistance per wire must not exce
ed 10 Ω
5.
To next device
Terminal
Description
Terminal Description
1
SLC in + and
SLC out (+)
4
Not used
2
SLC in −
5
Remote LED +
3
Not used
6
Remote LED −
and SLC out −
Specifications
Base diameter
Without trim ring
With trim ring
4.35 in. (110.49 mm)
6.0 in. (152 mm)
Height from box (including
detector)
2.08 in. (53 mm)
Maximum distance
Ceiling
Wall
Not less than 4 in. (100 mm) from the
sidewall
Between 4 and 12 in. (100 and
300 mm) from the ceiling
Wire size
12 to 18 AWG wire (0.75 to 2.5 mm²)
Compatible detectors
FX-PD, E-PD, FX-PHD, E-PHD,
FX-HD, E-HD, V-PS, V-PHS, V-HRD,
and V-HFD
Compatible electrical boxes
4 × 4 in. octagonal ring (mud box)
1-7/8 in. (47 mm) deep single-gang
box
4 in. square x 2-1/2 in. (64 mm) deep
box (requires using the included
adaptor bracket and trim ring)
Operating environment
Temperature
Relative humidity
32 to 120°F (0 to 49°C)
0 to 93% noncondensing
Storage temperature range
−4 to 140°F (−20 to 60°C)