CAMPO EQUIPMENT BLAZE 700 D/G Manuel d'utilisation
Page 6

MOTOR HP
4
4
4
Ductability
200ft
200ft
200ft
Outlet Duct Size
20” or (4) X 12”
20” or (4) X 12”
20” or (4) X 12”
Inlet Duct Size
20”
20”
20”
Gas Conversion
Easy switch over
Blue handle Ball
Valve on Gas
manifold.
Closed position:
Propane
Open position:
Natural Gas
N/A
Easy switch over
Blue handle Ball
Valve on Gas
manifold.
Closed position:
Propane
Open position:
Natural Gas
Manifold pressure “W.C.
2.5 (Pressure to be
set before NG/LP
switchover valve
and after adjusting
valve on manifold)
NOTE: If pressure
reading taken after
NG/LP switchover
valve then pressure
is to be 1.5”
N/A
2.7 (Pressure to
be set before
NG/LP switchover
valve and after
adjusting valve on
manifold)
NOTE: If pressure
reading taken
after NG/LP
switchover valve
then pressure is to
be 1”
Minimum/Maximum
Supply Pressure
“W.C.
8/12
N/A
8/12
Nozzle
N/A
4 GPH X 45 B
N/A
Pump Pressure
N/A
160 PSI
N/A
GPH
N/A
5 GPH
N/A
Fuel
NG or LP
No. 1 or No. 2 /
Kerosene or
Furnace Oil
NG or LP
CAMPO EQUIPMENT CO. LTD. (ECOBLAZE)
6 Carson Court, Brampton, ON, CANADA, L6T 4P8
Tel: (905) 793-2525 | Fax: (905) 793-8768
P a g e