Wired

Wired Sensorless Sensorless

Pressure Flow Pressure Flow

Parameter

Parameter Name

Set-up 1

Set-up 2

Set-up 3

Set-up 4

Parameter Description

Number

Defaults

Defaults

Defaults

Defaults

20-21

Setpoint 1

15.0

150.0

15.0

150.0

Process setpoint

20-00 Feedback 1 Source

Analog input 53

Sensorless

Sensorless Transducer feedback input

Pressure Flow

20-12

Ref/Feedb Unit

psi

GPM

psi

GPM

Transducer feedback units

20-13

Min Ref/Feedb.

0.0

0.0

Min feedback value for the transducer

20-14

Max Ref/Feedb.

40.0

300.0

40.0

300.0

Max feedback value for the transducer

3-41

Ramp 1 Up Time

10 s

Ramp up time (0 to full speed)

3-42

Ramp 1 Down Time

10 s

Ramp down time (full speed to 0)

20-93

PID Prop Gain

5

Proportional correction gain for PID

20-94

PID Integration Time

3.3 s

Integration time for the PID controller

22-80 Flow Compensation

Disabled

Flow compensation (friction head loss)

function

22-81 Square-Linear Cure

100%

Adjusts shape of the flow

Approx.

compensation control curve.

Speed needed for minimum head at no

22-84

Speed at No Flow [Hz]

0.0 Hz

NA

0.0 Hz

flow. Use when flow compensation is

enabled.

Speed needed to maintain the design

22-86

Speed at Design Point

60.0 Hz

NA

60.0 Hz

point. Use when flow compensation is

enabled.

22-87

Pressure at No Flow

0.00

Pressure at no flow speed. Use when

Speed

flow compensation is enabled.

22-89 Flow at Design Point

NA

NA

0.000

NA

System flow at the design point. Use

when flow compensation is enabled.

5-10

Digital Input 18

Start

DI 18 function

5-11

Digital Input 19

No Function

DI 19 function

5-12

Digital Input 27

No Function

DI 27 function

6-50

Terminal 42 Output

Speed 4-20mA

Analog output function

5-40

Function Relay

Relay 1: No Alarm

Relay 1 and 2 function

Relay 2: running

My Personal Menu parameters are shown in the following table:

• If using Set-up 1 or Set-up 2 a transducer is required

at AI53. Wire a 4-20mA transducer as shown:

• Wire a 0-10V transducer as shown: