VEGA VEGAFLEX 65 Foundation Fieldbus Manuel d'utilisation

Page 47

Advertising
background image

Diagramme du réglage
La figure suivante montre la fonction du réglage.

Secondary_value_1

Calibration

Lowest Point

Calibration

Highest Point

Sensor_value

cal_level_lo

cal_level_hi

Calibration
Lowest Point

Calibration
Highest Point

Sensor reference plane

cal_level_lo [%]

cal_level_hi [%]

Fig. 21: Réglage VEGAFLEX 65

Liste des paramètres
La liste suivante vous indique les paramètres les plus importants et leur signification :

l

primary_value

-

This is the process value after adjustment and Linearization with the status of the transducer
block

-

It is the input for the AIFB when CHANNEL = 1 is selected

-

The unit is defined in "primary_value_unit"

l

primary_value_unit

-

Selected unit code for "primary_value"

l

secondary_value_1

-

This is the process value after adjustment with the status of the transducer block

-

It is the input for the AIFB when CHANNEL = 2 is selected

-

The unit is defined in "secondary_value_2_unit"

l

secondary_value_1_unit

-

Selected unit code for "secondary_value_1"

VEGAFLEX 65 • Foundation Fieldbus

47

10 Annexe

31848

-

FR

-120507

Advertising