Product overview and specifications – Dell Metered PDU LED Manuel d'utilisation

Page 2

Advertising
background image

2

Dell Metered Rack Power Distribution Unit—Product Overview and Specifications

Product Overview and Specifications

The Dell Metered Rack PDU distributes power to the devices in the rack.

O

U T L E T S

— The Rack PDU has twenty (20) 5-15 R outlets.

P

O W E R

C O R D

— The Rack PDU has an IEC-320-C20 inlet and can be used with a detachable power cord (not provided).

G728N

Electrical

Input connection

IEC-320-C20

Acceptable input voltage

100–120 VAC

±

10%

Maximum input current (phase)

16 A

Input frequency

50/60 Hz

Input power

1.9 kVA UL and C-UL (derated), PSE

Output voltage

100–120 VAC (Line-to-Neutral)

Output connections

Twenty (20) 5-15 R

Maximum output current (outlet)

5-15 R: 12 A UL and C-UL (derated), PSE

Maximum output current (phase)

16 A UL and C-UL (derated), PSE

Physical

Dimensions
(H x W x D)

162.5 x 5.5 x 4.1 cm
(64.0 x 2.2 x 1.6 in)

Shipping dimensions
(H x W x D)

187.5 x 22.6 x 13.5 cm
(73.8 x 8.9 x 5.3 in)

Weight

4.1 kg (9.0 lb)

Shipping weight

5.9 kg (13.0 lb)

Environmental

Maximum elevation

(above MSL)

Operating

Storage

0 to 3048 m (0 to 10,000 ft)
0 to 15 240 m (0 to 50,000 ft)

Temperature

Operating

Storage

0 to 50°C (32 to 122°F)
–15 to 60°C (5 to 140°F)

Humidity

Operating

Storage

5 to 95%, non-condensing
5 to 95%, non-condensing