8. Specifications

PDFY-NMU-A series

Regarding transfer of installation

When removing and reinstalling the air conditioner when you enlarge your
home, remodel, or move, consult with your dealer in advance to ascertain the
cost of the professional engineering work required for transferring the installa-
tion.

Caution:

When moving or reinstalling the air conditioner, consult with your dealer.
Defective installation can result in electric shock, fire, etc.

Regarding noise

In installing work, choose a place that can fully bear the weight of the air con-
ditioner, and where noise and vibration can be reduced.

Choose a place where cool or warm air and noise from the outdoor air outlet of
the air conditioner does not inconvenience the neighbors.

If any alien object is placed near the outdoor air outlet of the air conditioner,
decreased performance and increased noise can result. Avoid placing any
obstacles adjacent to the air outlet.

If the air conditioner produces any abnormal sound, consult with your dealer.

Maintenance and inspection

If the air conditioner is used throughout several seasons, the insides can get
dirty, reducing the performance.

Depending upon the conditions of usage, foul odors can be generated and
drainage can deteriorate due to dust and dirt, etc.

Item

Model

PDFY-10NMU-A PDFY-16NMU-A PDFY-24NMU-A PDFY-32NMU-A PDFY-40NMU-A PDFY-48NMU-A

Capacity

Cooling

kW

2.8

4.6

6.9

9.1

11.9

13.6

*1

BTU/h

9500

15700

23600

31000

40500

46500

Heating

kW

3.2

5.5

7.4

10.0

13.2

15.0

BTU/h

10800

18700

25400

34000

45000

51000

Power sourse

~208-230V, 60Hz

Power input

Cooling

kW

0.12

0.15

0.17

0.21

0.29

0.39

Heating

kW

0.12

0.15

0.17

0.21

0.29

0.39

Current

Cooling

A

0.61-0.68

0.77-0.85

0.87-0.96

1.07-1.19

1.48-1.64

1.99-2.21

(208-230V)

Heating

A

0.61-0.68

0.77-0.85

0.87-0.96

1.07-1.19

1.48-1.64

1.99-2.21

Dimensions

Height

mm(in)

295 (11-5/8)

335 (13-7/32)

Width

mm(in)

710 (27-31/32)

960 (37-13/16)

1160 (45-11/16)

1510 (59-15/32)

Depth

mm(in)

735 (28-15/16)

775 (30-17/32)

Net weight

kg

25.5

32

39

52

lb

57

71

86

115

FAN

m

3

/min [cfm]

6.0-6.5-7.5-8.5 10.0-11.0-12.5-14.0 12.5-14.0-16.0-18.0 14.0-16.5-18.5-21.0

19.5-28.0

24.0-34.0

[211-229-264-300] [353-388-441-494] [441-494-565-635] [494-582-653-741]

[688-988]

[847-1200]

Pa [in.WG]

208V

30-50-80

30-50-80

30-50-80

30-50-100

50-100-130

50-100-130

[0.120-0.200-0.320] [0.120-0.200-0.320] [0.120-0.200-0.320] [0.120-0.200-0.401] [0.200-0.401-0.521] [0.200-0.401-0.521]

230V

40-60-100

40-60-100

40-60-100

40-60-115

60-115-150

60-115-150

[0.160-0.240-0.401] [0.160-0.240-0.401] [0.160-0.240-0.401] [0.160-0.240-0.461] [0.240-0.461-0.601] [0.240-0.461-0.601]

Noise level (Low-Middle2-Middle1-High)*3

208V

26-28-31-34

32-34-35-37

28-32-34-37

32-35-38-40

36-42

40-45

(208-230V)

dB(A)

230V

28-30-33-36

34-36-37-39

30-34-36-39

34-37-40-42

37-44

42-46

Filter

Standard filter

Airflow rate (Low-Mid-

dle2-Middle1-High)

External static pres-

sure*2 (208-230V)

Advertising