C7089 OUTDOOR SENSOR

3

69-1709EFS

OPERATION

Once installed and the Thermostat Installer Setup
Number 0340 is set to 1 or 2, the outside temperature
can be displayed on the thermostat. See Fig. 3.

Fig. 3. Outside temperature reading on

TH8000 Series Thermostat.

The C7089 Outdoor Sensor converts outdoor ambient
temperature to a resistance that the thermostat can
interpret.

The C7089 has a negative temperature coefficient (TC), which
means that resistance decreases as
the temperature increases. See Table 1.

CHECKOUT

Allow C7089B Outdoor Sensor to absorb outdoor air for a
minimum of twenty minutes before taking a reading.

With an accurate thermometer (±1°F [0.5°C]) measure
the temperature at the sensor location, allowing time for
the thermometer to stabilize before reading.

To verify sensor resistance, remove one wire from one of
the C7089 60-in. leadwires. Use an ohmmeter to
measure the resistance across the sensor. Then verify
the sensor accuracy with the temperature/resistance in
Table 1.

CALIBRATION

The C7089 Outdoor Sensor is calibrated at the factory and can-
not be recalibrated in the field.

Heat On

SCHED

HOLD

CLOCK SCREEN

MORE

MON

TUE

WED

THU

FRI

SAT

AAT

SUN

AM

FAN

AUTO

SYSTEM

HEAT

Following

Schedule

Outside

Set To

M19971

Table 1. Sensor Resistance

at Outdoor Temperature .

Outdoor Temperature

Ohms of

Resistance

°F

°C

-20

-28.9

106926

-18

-27.8

100923

-16

-26.7

95310

-14

-25.6

90058

-12

-24.4

85124

-10

-23.3

80485

-8

-22.2

76137

-6

-21.1

72060

-4

-20.0

68237

-2

-18.9

64631

0

-17.8

61246

2

-16.7

58066

4

-15.6

55077

6

-14.4

53358

8

-13.3

49598