Reznor EGHB Unit Installation Manual Manuel d'utilisation

Instructions ‘‘eghb’’ model, Attention

Advertising
background image

How to mount it.

KEEP THIS INSTRUCTION PAMPHLET

FOR THE USER - INS132-200711-03

INSTRUCTIONS

‘‘EGHB’’ Model

LOCATION OF HEATERS AND REMOTE

THERMOSTATS

1- For best results, do not exceed mounting heights as per

table below :

Maximum recommended mounting height :

2 - 10 kW

8 ft. (2.4 m)

15 - 30 kW

10 ft. (3.0 m)

40 - 60 kW

15 ft. (4.5 m)

2- Direct discharge air streams :

- Away from room occupants.

- Away from columns, posts, machinery and partitions.

- Parallel to outside walls.

- Along the windward side of buildings exposed

to prevailing winds.

3- Locate thermostats on interior partitions, walls or posts

(insulate from cold steel posts). Install thermostats away

from cold drafts, internal heat sources and from heater

discharge.

4- Small rooms require only one unit heater. In large rooms,

arrange multiple units to provide perimeter circulation as

illustrated in Fig. 1 and Fig. 2.

WARNING

- Disconnect all power supplies before working on circuit.

- Do not heat air containing combustible materials.

- Mount heater out of reach.

- Install at least 2 ft. (61 cm) from floor

except 40 - 60 kW at least 8 ft. (2.4 m) from floor.

Minimum clearance from walls and ceiling are :

2 - 10 kW

4 in. (10 cm)

15 - 30 kW

6 in. (15 cm)

40 - 60 kW

12 in. (30 cm)

MOUNTING EGHB 40 - 60 kW

4 hooks of suspension supplied

1/2 in -13 UNC threaded

rods not included

Hook of suspension

Fig. 1

Fig. 2

OVERTEMPERATURE PROTECTION

The motor and the electric heating elements are protected

against overtemperature by automatic reset thermal

high-limits. Cycling of either high-limit is an indication of

abnormal operation and should be corrected at once.

LUBRIFICATION OF MOTOR

The motor includes sealed lubrification-free bearings.

MAINTENANCE

Once a year, remove the dust accumulation inside the heater

using a vacuum cleaner or compressed air. Cleaning should be

done while the heater is disconnected from the supply circuit.

A qualified technician should perform any other servicing.

WARRANTY

The manufacturer warrants the electric heating element of the

EGHB Model for a one (1) year period ; and their component

parts against defects in material and workmanship for a one

(1) year period following the date of purchase, under normal

use and service, when proof of purchase of such is provided

to the manufacturer. The obligation of the manufacturer,

under the terms of this warranty, will be to supply a new unit

and this omits the manufacturer to bear the installation costs

or other secondary charges linked to replacing the unit or the

component part(s).

MOUNTING EGHB 2 - 30 kW

Horizontal wall or ceiling mounting

using 1 of 2 supplied brackets

which allow 360° rotation.

Vertical mounting

using 4 threaded rods

1/2 in - 13 UNC not included

Wall mounting

using the triangular braket.

Ceiling mounting

using the U-shaped bracket

Diffuser cone available

Fig. 3

Fig. 4

Reznor LLC

O’Fallon MO USA 63368

Tel.: 1 800 695-1901

www.ReznorHVAC.com

©

2014 Reznor, LLC. All rights reserved. All other trademarks are the

property of their respective organizations.

ATTENTION

Basic precautions should always be followed to reduce the

risk of fire, electric shock, and injury to persons.

- Read all instructions before using this heater.

- Disconnect all power supplies before working on circuit.

- Do not heat air containing combustible materials.

- Mount heater out of reach.

- Install at least 2ft. (61 cm) from floor

except 40 - 60 kW at least 8 ft. (2.4 m) from floor.

- Do not use outdoors.

- Do not insert or allow foreign objects to enter any

ventilation or exhaust opening as this may cause an

electric shock or fire, or damage the heater.

- Do not block air intakes or exhaust in any manner.

- Heater contains arcing and sparking parts. Do not use it in

areas where gasoline, paint, or flammable liquids are used

or stored.

- Use this heater only as described in this manual. Any other

use not recommended by the manufacturer may cause fire,

electric shock, or injury to persons.

POWER SUPPLY CONNECTIONS

The power supply may be single or three phase as shown on

the nameplate. The wiring diagram is on the inside of the

terminal compartment cover. Wire heater in accordance with

local and national codes.

TEST

- To test the unit heater, temporarily set thermostat to

maximum temperature.

- Make sure that the fan rotates in the correct direction;

airflow should be in the direction of the arrow such as

indicated on the Fig. 4.

THE INSTALLATION MUST BE EXECUTED

BY A QUALIFIED TECHNICIAN

RISK OF ELECTROCUTION