tekmar 518 Thermostat Quick Start Manuel d'utilisation

Page 4

Advertising
background image

Display

Setting

Installer settings. Press the and buttons together for 5 more seconds.

AUXILIARY SENSOR
Select the type of auxiliary sensor. Available when an auxiliary
sensor is automatically detected. NONE = no auxiliary sensor,
ROOM = Indoor Sensor, OUT = Outdoor Sensor, FLOR = Slab
Sensor

Room

ROOM SENSOR
Select if the built-in room temperature sensor is on or off. The built-
in room sensor can only be disabled when an auxiliary room or slab
sensor is connected.

F

MAX

FLOOR MAXIMUM
Set the floor maximum temperature in order to protect the floor
covering. Suggested settings: Tile = 90°F (32°C), Wood Floor =
85°F (29°C)

ESCAPE
Release the and buttons to return to the home screen.

For a full list of settings and operational details, please refer to the
thermostat Installation and Operation Manual 518_D that is available from
www.tekmarControls.com