Module indicators, Self-test – Rockwell Automation 1440-REX03-04RG XM-442 Voted EODS Relay Module Manuel d'utilisation

Page 7

Advertising
background image

Rockwell Automation Publication GMSI10-IN016C-EN-P - February 2014

7

XM-442 Voted EODS Relay Module

Module Indicators

The XM-442 module has three status indicators, which are on top of the module.

Module Status (MS) Indicator

Shutdown Relay Indicator

Alarm Relay Indicator

Self-Test

The XM-442 module performs a self-test at powerup. During the self-test, all of the indicators turn red for approximately 1
or 2 seconds. After the self-test has completed, the Module Status indicator changes from red to green if no fault is present,
and the Alarm and Shutdown indicators turn off.

Color

State

Description

No color

Off

No power applied to the module.

Green

Solid

Power applied to the module.

Red

Solid

An unrecoverable fault has occurred. It is possible that the module must be repaired or replaced.

Color

State

Description

Red

Off

On-board relays are not activated.

Solid

On-board relays are activated:
Overspeed condition on any two of the three EODS channels
Failure of a sensor, power supply, or logic device on any two of the three EODS channels (circuit fault)

Color

State

Description

Red

Off

On-board relay is not activated.

Solid

Onboard relay is activated:
Overspeed condition on any one of the three EODS channels
Failure of a sensor, power supply, or logic device on any one of the three EODS channels, or within the XM-442 module itself

(circuit fault)

Failure of the XM-442 module’s primary or secondary power supply

VOTED EODS RELAY

1440-REX03-04RG

Module Indicators