5

Publication 1794-IN100B-EN-P - June 2004

Output Specifications

Number of Outputs

1794-OE4, -OE4K - 4 single-ended, nonisolated
1794-IE4XOE2 - 2 single-ended, nonisolated

Resolution

Voltage

Current

12 bits plus sign
0.156mV/cnt
0.320

μΑ/cnt

Data Format

left justified, 16 bit 2’s complement

Conversion Type

Pulse width modulation

Output Current Terminal

0mA output until module is configured
4-20mA (user configurable
0-20mA (user configurable

Output Voltage Terminal

0V output until module is configured
+10V (user configurable)
0-10V user configurable)

Step Response to 63% -
Voltage or Current Terminal

24ms

Current Load on voltage output

3mA maximum

Absolute Accuracy

1

Voltage Terminal
Current Terminal

0.133% Full Scale @ 25°C
0.425% Full Scale @ 25°C

Accuracy Drift with
Temperature

Voltage Terminal

Current Terminal

0.0045% Full Scale/°C
0.0069% Full Scale/°C

Resistive Load on mA Output

15-750 ohm @ 24V dc

General Specifications for 1794-IE8, -IE8K, -OE4, -OE4K, and -IE4XOE2

Module Location

Cat. No. 1794-IE8, -IE8K, -IE4XOE2 - 1794-TB2, -TB3, -TB3S,
-TB3T, -TB3TS Terminal Base Unit
Cat. No. 1794-OE4, -OE4K - 1794-TB2, -TB3, -TB3S, -TB3T,
-TB3TS, and -TBN Terminal Base Unit

Terminal Base Screw Torque

7 pound-inches (0.8Nm)

9 pound-inches (1.0Nm) for 1794-TBN

Isolation Voltage

Tested at 850V dc for 1s between user power to system
No isolation between individual channels

External dc Power Supply

Voltage Range

Supply Current

24V dc nominal
10.5 to 31.2V dc (includes 5% ac ripple)
1794-IE8, -IB8K - 60mA @ 24V dc; 150mA @ 12V dc
1794-OE4, -OE4K - 70mA @ 24V dc; 150mA @ 12V dc
1794-IE4XOE2 - 70mA @ 24V dc; 150mA @ 12V dc

Dimensions (with module
installed)

31.8H x 3.7W x 2.1D inches
45.7H x 94W x 53.3D mm

Flexbus Current

20mA

Power Dissipation

1794-IE8, -IB8K - 3.0W maximum @ 31.2V dc
1794-OE4, -OE4K - 4.5W maximum @ 31.2V dc
1794-IE4XOE2 - 4.0W maximum @ 31.2V dc

Thermal Dissipation

1794-IE8, -IB8K - Maximum 10.2 BTU/hr @ 31.2V dc
1794-OE4, -OE4K - Maximum 13.6 BTU/hr @ 31.2V dc
1794-IE4XOE2 - Maximum 15.3 BTU/hr @ 31.2V d

Keyswitch Position

1794-IE8, -IB8K - 3
1794-OE4, -OE4K - 4
1794-IE4XOE2 - 5

Environmental Conditions

Operating Temperature

IEC 60068-2-1 (Test Ad, Operating Cold),
IEC 60068-2-2 (Test Bd, Operating Dry Heat),
IEC 60068-2-14 (Test Nb, Operating Thermal Shock):
0 to 55°C (32 to 131°F)

Storage Temperature

IEC 60068-2-1 (Test Ab, Un-packaged Non-operating Cold),
IEC 60068-2-2 (Test Bb, Un-packaged Non-operating Dry Heat),
IEC 60068-2-14 (Test Na, Un-packaged Non-operating Thermal
Shock):
–40 to 85°C (–40 to 185°F)

Relative Humidity

IEC 60068-2-30 (Test Db, Unpackaged Nonoperating

Damp Heat):
5 to 95% non-condensing

Vibration

IEC60068-2-6 (Test Fc, Operating):
5g @ 10-500Hz

Shock

IEC60068-2-27 (Test Ea, Unpackaged shock):
Operating 30g
Non-operating 50g

Emissions

CISPR 11
Group 1, Class A (with appropriate enclosure)

ESD Immunity

EC 61000-4-2:
4kV contact discharges
8kV air discharges

Radiated RF Immunity

IEC 61000-4-3:
10V/m with 1kHz sine-wave 80%AM from 30MHz to 1000MHz

Conducted RF Immunity

IEC 61000-4-6:
10V rms with with 1kHz sine-wave 80%AM from 150kHz to
30MHz

EFT/B Immunity

IEC 61000-4-4:
±2kV at 5kHz on signal ports

Surge Transient
Immunity

IEC 61000-4-5:
±2kV line-earth (CM) on shielded ports

Enclosure Type Rating

None (open-style)

Conductors

Wire Size

Category

2

22-12AWG (0.34mm

2

-2.5mm

2

) stranded copper wire rated at

75°C or higher
3/64 inch (1.2mm) insulation maximum
2

Certifications (when product
is marked)

3

UL

UL Listed Industrial Control Equipment

UL

UL Listed for Class I, Division 2 Group A,B,C,D

Hazardous Locations

C

UL

US

UL Listed Industrial Control Equipment, certified for US

and Canada (1794-IE8, -OE4)

C

UL

UL Listed for Class I, Division 2 Group A,B,C,D Hazardous

Locations, certified for Canada (1794-IE8, -IE8K, -OE4,

-OE4K)

CSA CSA certified Process Control Equipment

CSA CSA certified for Class I, Division 2, Groups A, B, C and D

Hazardous locations

EEx

3

European Union 94/9/EEC ATEX Directive, compliant

with:

EN 50021; Potentially Explosive Atmospheres,

Protection “n” (European Zone 2)

CE

3

European Union 89/336/EEC EMC Directive,

compliant with:

EN 61000-6-4; Industrial Emissions

EN 50082-2; Industrial Immunity

EN 61326; Meas./Control/Lab., Industrial Requirements

EN 61000-6-2; Industrial Immunity

C-Tick

3

- Australian Radiocommunications Act compliant with

AS/NZS CISPR 11, Industrial Emissions

1

Includes offset, gain, nonlinearity and repeatability error terms.

2

You use this category information for planning conductor routing as described in Allen-Bradley

publication 1770-4.1, Industrial Automation Wiring and Grounding Guidelines.

3

For the latest up-to-date information, see the Product Certification link at www.ab.com for Declarations of
Conformity, Certificates and other certification details. For notification of any additional release notes, refer to

www.ab.com/manuals/.

Advertising