Specifications – Rockwell Automation 1794-IRT8XT/B TC/MV/RTD Input Module Installation Instructions Manuel d'utilisation
Page 4
4
Publication 1794-IN050J-EN-P - January 2009
Output Map (Write)
Data Format for All Channels - Write Word 0
Fault Mode - Write Word 0
Reference Junction Selection - Write Word 0
Add-on Filter Selections - Write Word 0
Sensor Mode Select - Write Word 1
TC/RTD Input Type Selection - Write Word 1
Sensor Type Select - Write Word 1
RTD Offset Select - Write Word 2
Specifications
Word 9
Ch 7
Flt
Ch 6
Flt
Ch 5
Flt
Ch 4
Flt
Ch 3
Flt
Ch 2
Flt
Ch 1
Flt
Ch 0
Flt
CJC2
Alm
CJC1
Alm
SAB
CJC
Status
Reserved
Word 10
Command Response
Response Data
Where: SAB =
Series of unit; 0 = Series A, 1 = Series B
Alm = Alarm
Flt = Fault
Dec.
15
14
13
12
11
10
09
08
07
06
05
04
03
02
01
00
Oct.
17
16
15
14
13
12
11
10
07
06
05
04
03
02
01
00
Word 0
Reserved
Data Format
Flt
Mod
e Ch
4-7
Flt
Mod
e Ch
0-3
Reference Jct.
Filter Cutoff
Word 1
TC/RTD Ch
4-7
Sensor
Mode
Ch 4-7
Sensor Type
Ch 4-7
TC/RTD
Ch 0-3
Sensor
Mode
Ch 0-3
Sensor Type
Ch 0-3
Word 2
RTD Offset
Ch 7
RTD Offset
Ch 6
RTD Offset
Ch 5
RTD Offset
Ch 4
RTD
Offset
Ch 3
RTD Offset
Ch 2
RTD Offset
Ch 1
RTD Offset
Ch 0
Word 3
Command
Command Data
Bit
11
10
09
08
0
0
0
0
°C (implied decimal point XXXX.X)
0
0
0
1
°F (implied decimal point XXXX.X)
0
0
1
0
°K (implied decimal point XXXX.X)
0
0
1
1
-32767…+32767
0
1
0
0
0…65535
0101 thru 1111 not used
Module defaults to -4000…10000 in millivolt mode, and 0…5000 in ohms mode with implied decimal points (for
example, -40 mV, 0.01
Ω) whenever °C, °F or °K is selected.
Bit
06
Fault enable for channels 0…3
07
Fault enable for channels 4…7
0 = Disabled
1 = Enabled
Bits
3-5
Reference Junction - used when sensor select is set to thermocouple and
sensor mode is set to internal compensation. Sets a fixed reference junction
to compensate all thermocouple channels.
Bit 05
04
03
Reference
Junction
0
0
0
0 °C (32 °F)
0
0
1
20 °C (68 °F)
0
1
0
25 °C (77 °F)
0
1
1
30 °C (86 °F)
1
0
0
40 °C (104 °F)
1
0
1
50 °C (122 °F)
1
1
0
60 °C (140 °F)
1
1
1
70 °C )158 °F)
Bit
02
01
00
Filter Time Constants - Actual filtering depends on the
module’s mode of operation.
0
0
0
Hardware filtering only (default filtering)
0
0
1
25 ms
0
1
0
100 ms
0
1
1
250 ms
1
0
0
500 ms
1
0
1
1 s
1
1
0
2 s
1
1
1
5 s
Bit
05
04
Sensor mode for channels 0…3
Bit
13
12
Sensor mode for channels 4…7
Thermocouple
0
0
External compensation - uses cold junction sensors (Both CJC sensors must be used
when external compensation is selected.)
0
1
Internal compensation - uses the value selected for “reference junction selection”
1
0
No compensation (Data is referenced to 0 °C.)
1
1
Differential measurement between 2 channels (0-1, 2-3, 4-5, 6-7)
RTD
0
0
2-wire RTD no compensation
0
1
2-wire RTD with user selected compensation
1
0
3-wire RTD
1
1
4-wire RTD
Dec.
15
14
13
12
11
10
09
08
07
06
05
04
03
02
01
00
Oct.
17
16
15
14
13
12
11
10
07
06
05
04
03
02
01
00
Bit
07
06
Input type for channels 0…3
Bit
15
14
Input type for channels 4…7
0
0
Thermocouple
0
1
RTD
1
0
Not used
1
1
Not used
RTD Type
Bit
03
02
01
00
Sensor type for channels 0…3
Bit
11
10
09
08
Sensor type for channels 4…7
0
0
0
0
Resistance (default)
0
0
0
1
100
Ω Pt α = 0.00385 Euro -200…+870 °C(-328…+1598 °F)
0
0
1
0
200
Ω Pt α = 0.00385 Euro -200…+400 °C(-328…+752 °F)
0
0
1
1
100
Ω Pt α = 0.003916 U.S. -200…+630 °C(-328…+1166 °F)
0
1
0
0
200
Ω Pt α = 0.003916 U.S. -200…+400 °C(-328…+752 °F)
0
1
0
1
100
Ω Nickel -60…+250 °C(-76…+482 °F)
0
1
1
0
200
Ω Nickel -60…+200 °C(-76…+362) °F)
0
1
1
1
120
Ω Nickel -80…+320 °C(-112…+608 °F)
1
0
0
0
10
Ω Copper -200…+260 °C(-328…+470 °F)
1001 thru 1111 not used
Thermocouple Type
Bit
03
02
01
00
Sensor type for channels 0…3
Bit
11
10
09
08
Sensor type for channels 4…7
0
0
0
0
mV (default)
0
0
0
1
B
300…1800 °C
(572…3272 °F)
0
0
1
0
E
-270…1000 °C
(-454…1832 °F)
0
0
1
1
J
-210…1200 °C
(-346…2192 °F)
0
1
0
0
K
-270…1372 °C
(-454…2502 °F)
0
1
0
1
TXK/XK(L)-200…800 °C
(-328…1472 °F)
0
1
1
0
N
-270…1300 °C
(-450…2372 °F)
0
1
1
1
R
-50…1768 °C
(-58…3214 °F)
1
0
0
0
S
-50…1768 °C
(-58…3214 °F)
1
0
0
1
T
-270…400 °C
(-454…752 °F)
1010 thru 1111 not used
Bit
01
00
RTD Offset Select Bits - Channel 0
Bit
03
02
RTD Offset Select Bits - Channel 1
Bit
05
04
RTD Offset Select Bits - Channel 2
Bit
07
06
RTD Offset Select Bits - Channel 3
Bit
09
08
RTD Offset Select Bits - Channel 4
Bit
11
10
RTD Offset Select Bits - Channel 5
Bit
13
12
RTD Offset Select Bits - Channel 6
Bit
15
14
RTD Offset Select Bits - Channel 7
0
0
Use channel loop compensation value stored during calibration procedure for 2-wire RTD
(default = 0
Ω) - 15 Ω max (Note: Functional up to RTD = 484 Ω max with total lead
resistance = 15
Ω.
0
1
5
Ω (total lead resistance)
1
0
10
Ω (total lead resistance)
1
1
15
Ω (total lead resistance)
Specifications - 24V dc Analog Module, Cat. No. 1794-IRT8, -IRT8K, IRT8XT
Number of inputs
8 channels (2 groups of 4)
Module Location
Cat. No. 1794-TB3G, 1794-TB3GS, 1794-TB3GK Terminal Base Units
Nominal input voltage
ranges
-40…100 mV dc for thermocouples
0…325 mV for RTDs
mV (default)
Supported
thermocouple types
Type Range °C
Range °F
B
300…1800 °C
(572…3272 °F)
E
-270…1000 °C
(-454…1832 °F)
J
-210…1200 °C
(-346…2192 °F)
K
-270…1372 °C
(-454…2502 °F)
TXK/XK(L)-200…800 °C (-328…1472 °F)
N
-270…1300 °C
(-454…2372 °F)
R
-50…1768 °C
(-58…3214 °F)
S
-50…1768 °C
(-58…3214 °F)
T
-270…400 °C
(-454…752 °F)
Supported RTD types
Resistance
100
Ω Pt α = 0.00385 Euro -200…870 °C(-328…1598 °F)
200
Ω Pt α = 0.00385 Euro -200…400 °C(-328…752 °F)
100
Ω Pt α = 0.003916 U.S. -200…630 °C(-328…1166 °F)
100
Ω Pt α = 0.003916 U.S. -200…400 °C(-328…752 °F)
100
Ω Nickel -60…250 °C(-76…482 °F)
200
Ω Nickel -60…200 °C(-76…362) °F)
120
Ω Nickel -80…320 °C(-112…608 °F)
10
Ω Copper -200…260 °C(-328…470 °F)
Resolution
14 bits