Specifications – Rockwell Automation 1756-HIST2G FactoryTalk Historian ME 2.2 Installation Instructions Manuel d'utilisation

Page 24

Advertising
background image

24 FactoryTalk Historian Machine Edition Module

Publication

1756-IN106A-EN-P - March 2011

Specifications

Cat. No.

1756-HIST1G | 1756-HIST2G

Environmental Conditions

Operating
Temperature

IEC 60068-2-1 (Test Ad, Operating Cold),
IEC 60068-2-2 (Test Bd, Operating Dry Heat),
IEC 60068-2-14 (Test Nb, Operating Thermal Shock):
0…60 °C (32…140 °F)

Non-operating
Temperature

IEC 60068-2-1 (Test Ab, Unpackaged Non-operating Cold),
IEC 60068-2-2 (Test Bb, Unpackaged Non-operating Dry
Heat),
IEC 60068-2-14 (Test Na, Unpackaged Non-operating
Thermal Shock):
-40…85 °C (-40…185 °F)

Relative Humidity

IEC 60068-2-30 (Test Db, Unpackaged Damp Heat):
5…95% noncondensing

Vibration

IEC 60068-2-6 (Test Fc, Operating):
2g @ 10…500 Hz

Operating Shock

IEC 60068-2-27 (Test Ea, Unpackaged Shock):
30g

Non-operating
Shock

IEC 60068-2-27 (Test Ea, Unpackaged Shock):
50g

Emissions

CISPR 11:
Group 1, Class A

ESD Immunity

IEC 61000-4-2:
4kV contact discharges
8kV air discharges

Radiated RF
Immunity

IEC 61000-4-3:
10V/m with 1 kHz sine-wave 80% AM from 80…2000MHz
1V/m with 1 kHz sine-wave 80% AM from
2000…2700MHz

EFT/B Immunity

IEC 61000-4-4:
±1 kV at 5 kHz on communications ports

Surge Transient
Immunity

IEC 61000-4-5:
±1 kV line-earth(CM) on communications ports

Conducted RF
Immunity

IEC 61000-4-6:
10V/rms with 1 kHz sine-wave 80% AM from 150
kHz…80MHz