INSTRUCTION SHEET

BULLETIN 1109 VACUUM STARTER

CURRENT RATINGS 600A

200V-1500V

- - - - - - - -

- - - - - - - -

- - - - - - - -

- - - - - - - -

- - - - - - - -

2

4

REVISION

AUTHORIZATION

DIMENSIONS APPLY BEFORE

SURFACE TREATMENT

H

A

B

C

D

E

F

G

(DIMENSIONS IN INCHES)

TOLERANCES UNLESS

OTHERWISE SPECIFIED

REFERENCE

SHEET

OF

DWG.

B

DR.

CHKD.

APPD.

DATE

DATE

DATE

±

±

±

ANGLES:

.XXX:

.XX:

LOCATION : MILWAUKEE,

WISCONSIN

U.S.A.

SIZE

1

2

3

4

5

6

7

8

E - DOC

THIS DRAWING IS THE PROPERTY OF

ROCKWELL AUTOMATION, INC.

OR ITS SUBSIDIARIES AND MAY NOT BE COPIED,

USED OR DISCLOSED FOR ANY PURPOSE

EXCEPT AS AUTHORIZED IN WRITING BY

ROCKWELL AUTOMATION, INC.

1022117

2

(2)

IMPORTANT: When ordering heater elements, specify the desired "Heater Type No.".
MOTORS RATED FOR CONTINUOUS DUTY WITH MARKED SERVICE FACTOR NOT LESS THAN 1.15 OR MARKED TEMPERATURE RISE NOT
OVER 40 C.
Select the "Heater Type No." with the listed "Full Load Amps."nearest the full load. Select the "Heater Type No." with the listed "Full Load
Amps."nearest the full load current value shown on the motor nameplate when the ambient temperature at the controller and the motor is the
same. If the ambient temperature at the controller is higher than at the motor and nameplate full load current is between the values listed, select
the "Heater Type No." with the higher value

. If the ambient temperature at the controller is lower than at the motor and the nameplate full

load current is between the values listed, select the Heater Type No." with the lower value

.

When temperature difference exceeds 10

˚

C (18

˚

F), consult local Allen-Bradley Office.

ALL OTHER MOTORS RATED FOR CONTINUOUS DUTY (INCLUDES MOTORS WITH MARKED SERVICE FACTOR OF 1.0).
Select the "Heater Type No." one rating smaller than determined by the above rules. This will provide protection at current levels 10% lower.
MOTORS RATED FOR INTERMITTENT DUTY:
Consult local Allen-Bradley Office.
The rating of the relay at 40˚ C is 115% of the "Full Load Amps." listed for "Heater Type No.".

SELECTION OF THE CLASS NUMBER OF OVERLOAD RELAY WITH ITS CORRESPONDING HEATER ELEMENT TYPE.

IMPORTANT: The overload relay on this controller can be arranged to have time-current characteristic (trip time) for either Class 10,

1Class 20or Class 30

relay performance depending upon the heater element type selected.
Standard Overload Protection: Class 20 relay performance

➋ can be obtained for general applications when using Type W heater elements. Refer to

the instructions and forms accompanying the controller for the selection of the correct Type W heater number and other application data.
Special Overload Protection:
A.
When Class 30 relay performance

➋ is desired, refer to the instruction data applicable for the Type WL heater elements.

NOTE: Type WL heater elements are for motors driving high inertia loads requiring additional accelerating times.
B. When Class 10 relay perfomance

➋ is desired, refer to the instructiondata applicable for the Type J heater elements.

NOTE: Type J heater elements are for hermetic motors and motorswith short locked-rotor times.
➊ The relay class number (10, 20, or 30) defines the maximum time in seconds at which the relay will trip when carrying 600% of its currentrating at 40°C
ambient temperature.
ATTENTION: For the class of relay performance selected, in order to avoid potential motor damage and/or premature motor failures: the motors to be
protected must have a safe permissible locked-rotor time equal to or greater than the trip time of the overload relay at locked-rotor current. Refer to motor
nameplate, motor manufacturer’s publications, or consult the motor manufacturer for this information.

SELECTION OF THE CLASS NUMBER OF OVERLOAD RELAY WITH ITS CORRESPONDING HEATER ELEMENT TYPE.

Select the Motor Branch Circuit Overcurrent Protection inaccordance with Applicable Electrical Code for W, WL, and J Heaters, except J Heaters have the
following restrictions:
A.The rating of the non-time delay fuse shall not exceed 300% of the motor full load amperes.
B.The rating of the time-delay fuse shall not exceed 175% of the motor full load amperes.

SELECTION OF WL HEATER ELEMENTS: Using the listed "Full Load Amps." from the Type W heater element table for the controller being applied, select
the desired "Heater Type No.". Add the letter L after the W to specify the "Type WL Heater No." required.The rating of the relay at 40

°C when using the Type

WL Heater Elements is 120% of the "Full Load Amps." listed for the corresponding Type W "Heater Type No.".
WYE-DELTA (Y

) APPLICATIONS: Divide the Motor Full Load Amperes by 1.73-use this value toselect the proper "Heater Type No.".

IMPORTANT:

Pour commander des éléments chauffants, préciser le «Type d'élém. chauff.»

MOTEURS HOMOLOGUÉS POUR SERVICE CONTINU, DONT LE FACTEUR DE SERVICE INDIQUÉ N'EST PAS INFÉRIEUR À 1.15 OU DONT
L'ÉLÉVATION DE TEMPÉRATURE INDIQUÉE N'EST PAS SUPÉRIEURE À 40

˚

C.

Choisir le «Type d'élém. chauff.» dont le «courant de pleine charge» est le plus proche de la valeur de pleine charge. Choisir le «Type d'élém. chauff.»
dont le «courant de pleine charge» répertorié est le plus proche de la valeur de courant de pleine charge indiquée sur la plaque signalétique du moteur
quand la température ambiante au contrôleur et au moteur est la même. Si la température ambiante au contrôleur est supérieure à la température
ambiante au moteur et que le courant de pleine charge sur la plaque signalétique se situe entre les valeurs répertoriées, choisir le «Type d'élém.
chauff.» de valeur supérieure

. Si la température ambiante au contrôleur est inférieure à la température ambiante au moteur et que le courant de

pleine charge sur la plaque signalétique se situe entre les valeurs répertoriées, choisir le «Type d'élém. chauff.» de valeur inférieure

.

Si l'écart de température dépasse 10

˚

C (18

˚

F), communiquer avec le bureau Allen-Bradley local.

TOUS LES AUTRES MOTEURS HOMOLOGUÉS POUR LE SERVICE CONTINU (CE QUI COMPREND LES MOTEURS AVEC UN FACTEUR DE
SERVICE INDIQUÉ DE 1.0).
Choisir le «Type d'élém. chauff.» dont la valeur nominale est d'un niveau plus bas que celle établie selon les instructions ci-dessus. Cette façon de
procéder permettra d'assurer une protection jusqu'à des niveaux de 10 % plus bas.
MOTEURS HOMOLOGUÉS POUR SERVICE INTERMITTENT :
Communiquer avec le bureau Allen-Bradley local. Les caractéristiques nominales du relais à 40

˚

C

TABLE 196

Heater

Type

No.

Full

Load

Amps

Heater

Type

No.

Full

Load

Amps

195
220
239
260
285
315
340
375
410

J7
J8
J9

J10
J11
J12
J13
J14
J15

J16
J17
J18
J19
J20

450
495
540
590
640

W26
W27
W28
W29
W30
W31
W32
W33
W34
W35

W36
W37
W38
W39
W40
W41
W42
W43
W44

Heater

Type

No.

Full

Load

Amps

Heater

Type

No.

Full

Load

Amps

115
125
135
147
165
179
196
216
232
260

287
315
350
385
420
465
515
570
630

TABLE 195

Eutectic Overload Relay
Relais de surchage en alliage
1109-DO_