Mounting

The signal conditioners are mounted on standard TS 35 rails.

5.

Electrical connection

5.1 Technical Data
Supply voltage

18 ... 30 Vdc/approx. 1 W

Operating temperature

0 °C ... +55 °C

Voltage supply via cross-connections. Operating carrying capacity of
cross-connection

Յ 2 A

Terminal assignments

1 Supply voltage to the bridge +
2 Supply voltage to the bridge -
3 Not assigned
4 Input +
5 Input -
6 Not assigned
7 Output 0/4...20 mA
8 Output 0...5/10 V
9 Output 0 V- reference potential

10 Power supply + 24 Vdc (cross-connected)
11 Power supply - GND (cross-connected)
12 Not assigned

Wire cross-section max. 2.5 mm

2

Multi-wire conncection max. 1 mm

2

(two wires with same cross-section)

7 8

10

1 2 3

9

11 12

4

5

6

Advertising