16

No power at
the sensor

Lights do not
switch ON

breaker has tripped,
is not switched ON, or
break in wiring

short circuit

low voltage wiring to
power pack is incorrect

light level setting is in
nighttime mode during
daytime operation

lamp burned out

power is off

breaker has tripped

detection zone not
correctly adjusted

power pack is in manual
on mode when being
used with a line voltage
switch

reset breaker, check
wiring with voltage
tester

check for proper
wiring connections

check for proper
wiring connections

adjust light level
setting

replace lamp

turn power on at
circuit breaker

reset breaker

readjust

place power pack in
the auto on mode

Problem

Cause

Remedy

Troubleshooting

17

Troubleshooting

Lights do not
switch OFF

Lights keep
switching
ON/OFF

Lights switch
ON without
obvious
movement

Sensor detects
occupancy but
turns off in 2
seconds

abundant heat from
fixture is within detection
zone and keeps lights
on as a result of
temperature change

continuous movement in
the detection zone

switched on light is
within detection zone

low voltage overload on
power pack

sensor is detecting
movement outside of the
lighting zone

sensor is in pulse mode
but is not connected to a
time delay relay

move sensor away
from direct view of
the fixture

readjust zone or
apply shroud

adjust detection
zone or apply
shrouds, increase
distance

reduce the
number of devices
connected to the
power pack

adjust zone or
apply shrouds

adjust sensor’s time
delay or use with a
time delay relay

Problem

Cause

Remedy