Maintenance – Edwards Signaling 869 Manuel d'utilisation

Page 2

Advertising
background image

4.

Connect the signaling circuit field wires to the terminals
(Figures 2 and 3).Polarity must be observed for units operating
on 24 VDC.

5.

Mount horn assembly on the mounting plate (Figure 1).

a.

The inside of the top of the grille has hinges that pass
through cutouts and engage with tabs on the mounting
plate. With the bottom of the grille lifted out slightly,
place the grille over the mounting plate so that the hinges
of the grille are in the mounting cutouts.

b.

Properly seat the grille by pressing the bottom in.

c.

Fasten the bottom of the grille to the mounting plate by
installing the captive combination drive screw.

6.

Apply power and activate the horn unit to verify that it is
operating properly.

Maintenance

CAUTION

Should the unit fail to operate properly, do not attempt
repair. Contact the supplier for replacement.

Perform a visual inspection and an operational test twice a year.

Figure 2. Wiring Diagrams

Figure 3. Terminal Block

Table 2. Specifications

P-047550-1785 ISSUE 2

N5 Model

AQ Model

Operating Voltage*

120V AC 50/60 Hz

24V AC 50/60 Hz

24V DC

Operating Current

24 mA

72 mA

22 mA

Sound Level Output at
10 feet (3.05 m)

Anechoic Chamber

96 dBA

Operating Environment

Indoor

93% @ 104F (40C) relative humidity; 32 to 120F (0 to

49C) variable ambient temperature

Outdoor

98% @ 104F (40C) relative humidity; 31 to 150F (-35 to

66C) variable ambient temperature

*The operating voltage to the horn may be continuous or coded such as march time or a

temporal pattern meeting ISO8201 (ANSI S3.41) Audible Emergency Evacuation Signal.