SA-CLA Class A Interface Card
Installation Sheet

EN FR


EN: Installation Sheet

Operation

The SA-CLA card allows NAC Class A wiring of the 64 point
control panel. The card's terminal block provides the wiring
connection for the NAC Class A return.

Installation

The Class A card is installed directly onto the control panel
circuit board using plastic standoffs and a plug connector.

To install the Class A card:

1. Power down the panel and disconnect the batteries.

2. Locate connector J2 (at the bottom-right of the main circuit

board).

3. Connect the card to connector J2 as shown in the diagram

below. Make sure you properly align the connector pins
and plastic mounting standoffs.

4. Connect the field wiring. See “Wiring.”

5. Power up the panel and connect the batteries.

Figure 1: SA-CLA installation

Connector J2

Class A card

Plastic mounting standoffs

Bottom-right of
main circuit
board

Wiring

The wiring connections on the Class A card are used when
wiring NACs Class A.

Figure 2: SA-CLA wiring

Class A card installed
on main circuit board

NAC1–

NAC2+

NAC2–

NAC1+

+

+

TB2 on main
circuit board

Specifications

Operating voltage

24 VDC

Operating current

Standby: 3 mA
Alarm/Max.: 60 mA

Max. resistance

26 Ω

Max. capacitance

0.35 µF

Max. current

2.5 A per circuit

Terminal rating

12 to 18 AWG (0.75 to 2.5 mm

2

)

Ground fault impedance

0 to 5 kΩ

Operating environment

Temperature

Humidity

32 to 120°F (0 to 49°C)
0 to 93% RH, noncondensing at
90°F (32°C)