IB4U Analog Isolator Detector Base
Installation Sheet

EN FR


EN: Installation Sheet

Operation

The IB4U Analog Isolator Detector Base is used to protect a
Class A SLC from total collapse due to wire-to-wire short
circuits. This is accomplished by isolating the part of the loop
containing the short from the remainder of the circuit. When the
cause of the short circuit is corrected, restore the loop by
resetting the control panel.

The base does not require a separate address because it
shares the address of the device it is connected to.

Installation

Cautions

To avoid accidental damage to the panel, disconnect all
power before wiring the unit.

Electrical supervision requires the wire run to be broken at
each terminal. Do not loop the signaling circuit field wires
around the terminals.

To install the base:

1. Install a compatible electrical box, and then pull all wiring

into the box.

2. Make all wiring connections as shown in “Wiring” below.

3. Attach the base plate to the electrical box using the

screws provided with the electrical box.

4. Attach the trim ring to the base plate. Align the marks on

the trim ring and base plate, press the trim ring onto the
base plate, and the rotate the trim ring until it locks into
place.

5. Attach the desired detector to the base. Align the arrows

on the detector and trim ring, press the detector into the
base, and then rotate the detector until it locks into place.

6. Apply power and activate the unit to verify that it is

operating properly.

Figure 1: Base installation

1.

Detector

2.

Trim ring

3.

Screw

4.

Base plate

5.

Compatible electrical box

Wiring

Wire in accordance with NFPA 72 and CAN/ULC-S524. Be
sure to observe the polarity of the terminals on the terminal
block as shown in the diagram.

Break the wire run at each terminal. Do not loop signaling
circuit field wires around terminals.

Note:

Shielded wire is required only in environments with very

high electrical noise. When you use shielded cable, follow
these recommendations:

Shield connection to and from the base must be
continuous and must be insulated from ground. Insulate
the shield using tape.

For Class B wiring, there is no shield connection to ground
at the last device.