R-LED Remote Alarm Indicator Installation Sheet

EN FR


EN: Installation Sheet

Operation

The remote LED alarm indicator is a polarized device that
provides visual indication when a detector initiates an alarm. A
clear lens, light emitting diode pulses on and off in case of an
alarm condition.

Installation

WARNINGS

This remote annunciator is not intended to be used as an
evacuation signal for Life Safety situations.

This remote annunciator will not operate if the device that
it is connected to it is not powered.

The LED used in this device has a 180° range of visibility,
but the best visibility is achieved in direct viewing
applications. This device should not be installed in areas
of direct sunlight, or where its intensity may be reduced.

Notes

The R-LED can only be used with the Standard Detector
Base, model B4U. It is not compatible with any other
bases.

This device is not for use with 24 VDC circuits.

To install the LED alarm indicator:

1. Verify that all field wiring is free of opens, shorts, and

ground faults.

2. Make all wiring connections shown in “R-LED wiring.”

3. Using the two machine screws provided, mount the LED

alarm indicator to a compatible electrical box.

R-LED wiring

To wire the R-LED:

Wire in accordance with NFPA 72 and CAN/ULC-S524. Be
sure to observe the polarity of the wires as shown in Figure 1.

Figure 1: R-LED wiring

Compatible detector base

or duct smoke detector

Specifications

Operating power

Voltage
Current


3 VDC
2 mA (3.5 mA max.)
175 µA average

Resistance per wire

10

Ω max.

Operating environment

Temperature
Humidity


32 to 120°F (0 to 49°C)
0 to 93% RH, noncondensing at 90°F
(32°C)

Operation

Pulses on alarm condition

Luminous intensity

65 mcd

LED type

Clear lens, red light emitting diode

Storage temperature
range

-4 to 140°F (-20 to 60°C)

Compatible detectors

FX-PD, E-PD, FX-PHD, E-PHD, FX-HD,
E-HD, V-PS, V-PHS, V-HRD, and V-HFD

Compatible bases

B4U standard base

Compatible duct detectors

FX-PDD, E-PDD

Compatible electrical
boxes

North American 1-gang box

Standard 4 in. square box 1-1/2 in.
(38 mm) deep with 1-gang cover

Wire size

12, 14, 16, or 18 AWG wire (2.5, 1.5, 1.0,
or 0.75 sq. mm) (Sizes 16 and 18 AWG
are preferred)