Response:

Paramètres

Length

Code/Data

Report Level (and Temperature)

6 characters ASCII

UuuNnn

Assign Unit Number

Request:

Paramètres

Length

Code/Data

Assign Unit Number

6 characters ASCII

UuuNnn

Response:

Paramètres

Length

Code/Data

Assign Unit Number

6 characters ASCII

UuuNOK
uu = new Address

Set number of Floats

Request:

Paramètres

Length

Code/Data

Set number of Floats

5 characters ASCII

UuuFn

Response:

Paramètres

Length

Code/Data

Set number of Floats

6 characters ASCII

UuuFOK

Si le nombre est remis à 0, le niveau n'est pas signalé.

Set Baud Rate

Request:

Paramètres

Length

Code/Data

Set Baud Rate

8 (12) characters ASCII

UuuBbbbb[b][pds]
Bbbbb[b] = 1200, 9600 (default)
pds = parity, data length, stop bit

(optional)
parity: none = 81, even = 71 (de-

fault), odd = 71

Response:

Paramètres

Length

Code/Data

Set Baud Rate

11 characters ASCII

Exemple : U01B9600E71
Modifier l'appareil à l'adresse 1 en vitesse de transmission 9600, parité paire, 7 bits de données, 1

bit d'arrêt