10 Annexe

VEGABAR 52 • Foundation Fieldbus

36720-FR-130410

– Highest calibrated value. For calibration of the high limit point you give the high measurement

value (pressure) to the sensor and transfer this point as HIGH to the transmitter. Unit derives

from 'Sensor_range.unit'

CAL_POINT_LO

– Lowest calibrated value. For calibration of the low limit point you give the low measurement

value (pressure) to the sensor and transfer this point as LOW to the transmitter. Unit derives

from 'Sensor_range.unit'

CAL_MIN_SPAN

– Minimum calibration span value allowed. Necessary to ensure that when calibration is done,

the two calibrated points (high and low) are not too close together. Unit derives from 'Sen-

sor_range.unit'

SCALE_IN

– Min/max-adjustment: Upper and lower calibrated points of the sensor. Unit derives from 'Sen-

sor_range.unit'

trimmed_value

– Sensor value after the trim processing. Unit derives from 'Sensor_range.unit'

sensor_sn

– Sensor serial number

temperature

– Process temperature. Selected as input to AIFB by setting 'Channel' = 4. Unit derives from

'Temperature.unit'

temperature_unit

– Unit code of 'Temperature', 'Max/Min_peak_temperature_value'

– °C, °F, K, °R

max_peak_temperature_value

– Holds the maximum process temperature. Write access resets to current value. Unit derives

from 'Temperature.unit'

– Write access resets to current value

min_peak_temperature_value

– Holds the minimum process temperature. Write access resets to current value. Unit derives

from 'Temperature.unit'

– Write access resets to current value

10.3 Encombrement

Les dessins cotés suivants ne représentent qu'une partie des versions possibles. Vous pouvez

télécharger des dessins cotés détaillés surwww.vega.com sous "Téléchargements" et "Dessins".
Les boîtiers à deux chambres ne sont disponibles qu'en version Ex-d pour les appareils avec sortie

signal 4 … 20 mA.