INSTALLATION

If the thermostat is used with unit heaters, the following
suggestions may help. (See Fig. 2).

1. Position “A” is good if it is sufficiently close to the unit

heater so that the return air to the heater flows over the
thermostat.

2. Position “B” is good if it is not necessary to make

frequent adjustments of the dial setting.

3. Position “C” is all right if it is sufficiently far from the

heater that air flowing over the thermostat is not much
above the average room temperature.

4. In general, position “D” is not advisable because the

post may prevent air from circulating over the thermo-
stat.

WIRING

All wiring should be done in accordance with local and national electrical codes and ordinances.

Figure 2

A

C

D

B

CEILING

POST

RETURN AIR

FLOOR

UNIT

PARTITION
WALL OR POST
DIRECTLY BEHIND
UNIT

ELECTRIC HEATER

ROOM
THERMOSTAT

ROOM
THERMOSTAT

SUPPLY

TYPE
11B09

TYPE
11B09

TYPE
11B09

RETURN

Diagram showing a single room thermostat controlling
several steam or hot water unit heaters. Any number of
unit heaters can be operated from one thermostat pro-
vided that the sum of the motor locked rotor currents or
the sum of the full load currents does not exceed the
electrical rating of the thermostat. The Type 11B09
Reverse-acting Surface Hot Water Control is used to
prevent operation of the fans when the steam is off or
when the water temperature is too low for proper heating.

The diagram at the right shows a heavy duty line voltage
room thermostat controlling an electric heater.

Figure 3

Figure 3A