RHFE-1004FA ENERGYSAVER CONVERSION
The conversion shall be carried out in accordance with the requirements of provincial authorities having jurisdiction
and in accordance with the requirements of the CAN1-B149.1 and 2 installation code. The appliance shall only be
converted to a gas for which it has been approved. Conversion kit shall be installed by a qualified service agency.
Front panel must be removed to access internal parts. Conversion kit are included in the carton box. Caution the gas
supply shall be shut off prior to disconnecting the electrical power, before proceeding with the conversion. Locate
orifices at burner end of gas tubes.
TECHNICAL DATA
– 1 –
BURNER ORIFICES
GAS CONVERSION SPECIFICATIONS
GAS SUPPLY PRESSURE
• The minimum inlet gas supply pressures is for the purpose of input adjustment.
• Heaters may be converted from one gas to another using Rinnai conversion kits.
• Output efficiency is 80% of rated input for Canadian installations.
WEIGHT
DIMENSIONS
GAS RATE (BTU/h)
90 Lbs.
Width: 36 5/8"
Height:26 3/8"
Depth: 12 3/8"
INPUT
NAT.
LPG
LOW
10,500 10,500
HIGH
38,400 36,500
OUTPUT
NAT.
LPG
LOW
8,400
8,400
HIGH
30,720 29,200
NAT.
QTY’
2
1
PARTS No.
LPG
HI
LOW
1004F-2031-B-1.80
1004F-2036-B-1.95
QTY’
2
1
PARTS No.
1004F-2031-A-0.95
1004F-2036-A-1.20
RHFE-1004FA-P
(Normal Altitude)
RHFE-1004FA-P
(High Altitude)
RHFE-1004FA-N
(Normal Altitude)
RHFE-1004FA-N
(High Altitude)
MODEL
GAS
TYPE
DIAMETER OF
ORIFICES
INCHES (mm)
DAMPER
ADJUSTMENT
LPG
NAT.
0.037
(0.95)
0.047
(1.20)
10/10
10/10
10/10
0.071
(1.80)
0.077
(1.95)
7/10
10/10
10/10
MANIFOLD
DIFFERENTIAL
PRESSURE
HI
HI
LOW
FRONT
RIGHT
LEFT
LOW
10.1"W.C.
7.3"W.C.
3.7"W.C.
2.7"W.C.
4.3"W.C.
4.3"W.C.
2.0"W.C.
2.0"W.C.
MINIMUM
MAXIMUM
NAT.
5.0"W.C.
10.5"W.C.
LPG
11.0"W.C.
13.0"W.C.
CONVERSION MANUAL : RHFE-1004FA
NAT.GAS to LPGAS
LPGAS to NAT.GAS
"WARNING"
This conversion kit shall be installed by a qualified service agency in accordance with the manufacture’s instructions
and appliance codes and requirement of the authority having jurisdiction. If the information in these instructions is not
followed exactly, a fire, explosion or production of carbon monoxide may result causing property damage, personal
injury or loss of life. The qualified service agency is responsible for the proper installation of this kit. The installation
is not proper and complete until the operation of the converted appliance is checked as specified in the
manufacture’s instructions supplied with the kit.