GV100W BOILER

INSTALLATION & OPERATING INSTRUCTIONS

Nominal Iron

Pipe length

Pipe Size

10'

20'

30'

40'

50'

60'

80'

100'

150'

3⁄4"

278

190

152

130

115

105

90

79

64

1"

520

350

285

245

215

195

170

150

120

11⁄4"

1050

730

590

500

440

400

350

305

250

11⁄2"

1600

1100

890

760

670

610

530

460

380

Note: Maximum pipe capacity in ft

3

/hr based on 0.60 specific gravity

gas at pressures of 0.5 psig or less and a 0.3 " WC pressure drop.

TABLE 3 Maximum Gas Pipe Capacity in ft

3

/hr

TABLE 4 Equivalent Pipe Length Chart

Equivalent length of pipe fittings in feet

Nominal Iron

Type of Pipe Fitting

Pipe Size

90° Elbow

Tee

Gate Valve

Gas Cocks

(branch flow)

(full port)

3⁄4"

2.06

4.12

0.48

1.25

1"

2.62

5.24

0.61

1.60

11⁄4"

3.45

6.90

0.81

2.15

11⁄2"

4.02

8.04

0.94

2.50

ELECTRICAL WIRING

Electrical Power Connections

CAUTION: Label all wires prior to disconnection when
servicing controls. Wiring errors can cause improper and
dangerous operation!

ATTENTION: Au moment de l’entretien des commandes,
étiquetez tous les fils avant de les débrancher. Des erreurs
de câblage peuvent entraîner un fonctionnement in-adéquat
et dangereux. S’assurer que l’appareil fonc-tionne
adéquatement une fois l’entretirn terminé.

Page 13

GV100W BOILER

INSTALLATION & OPERATING INSTRUCTIONS

The electrical connections to this boiler must be made in
accordance with all applicable local codes and the latest edition
of the National Electrical Code, ANSI/NFPA-70. Installation
should also conform with CSA C22.1 Canadian Electrical
Code Part I if installed in Canada. Install a separate 120 volt 15
amp circuit for the boiler. A shut-off switch should be located at
the boiler. The boilermust be grounded in accordance with the
authority having jurisdiction, or if none, the latest edition of the
National Electrical Code, ANSI/NFPA-70.

Line voltage field wiring of controls and other devices must
conform to the temperature limitation of type T wire at 95°F,
35°C, above room temperature. Use copper conductors with a
minimum size of #14 awg. Low voltage wiring must not be less
than #18 awg with a neoprene, thermoplastic or other
equivalent insulation having a minimum insulation thickness of
0.012 in,

0.3 mm.

THERMOSTAT INSTALLATION

Always follow the instructions included with the thermostat to
be used to control the boiler. Proper location of the thermostat
will ensure efficient trouble-free operation of the boiler. Mount
the thermostat to an inside wall at a height approximately five
feet above the floor. Avoid placing the thermostat in areas that
will not provide an accurate measurement of the room
temperature. Locating the thermostat behind a door, in an alcove,
close to a source of thermal radiation or in a drafty area will
cause poor or sporadic heating.

CO DETECTORS

WARNING: Installers must follow local regulations with
respect to the installation of CO detectors and follow
the manufacturer’s stated maintenance schedule for
this boiler!

ATTENTION: Observer les règlements règional à l'egard
des détecteurs de monoxyde de carbone et observer
entretien de manufacturier pour cette chaudière!