Warning – Faber Inca Pro 30 Manuel d'utilisation

Page 2

Advertising
background image

Version 10/05 - Page 2

VENTING REQUIREMENTS

Determine which venting method is best for your application.

Ductwork can extend either through the wall or the roof.

The length of the ductwork and the number of elbows should

be kept to a minimum to provide efficient performance. The

size of the ductwork should be uniform. Do not install two el-

bows together. Use duct tape to seal all joints in the ductwork

system. Use caulking to seal exterior wall or floor opening

around the cap.

Flexible ductwork is not recommended. Flexible ductwork

creates back pressure and air turbulence that greatly

reduces performance.

Make sure there is proper clearance within the wall or floor for

exhaust duct before making cutouts. Do not cut a joist or stud

unless absolutely necessary. If a joist or stud must be cut, then

a supporting frame must be constructed.

FOR MORE SPECIFIC DUCTWORK INFORMATION, GO

TO PAGE 6.

WARNING - To Reduce The Risk Of Fire, Use Only Metal

Ductwork.

ELECTRICAL REQUIREMENTS

A 120 volt, 60 Hz AC-only electrical supply is required on a sepa-

rate 15 amp fused circuit. A time-delay fuse or circuit breaker

is recommended. The fuse must be sized per local codes in

accordance with the electrical rating of this unit as specified

on the serial/rating plate located inside the unit near the field

wiring compartment. THIS UNIT MUST BE CONNECTED

WITH COPPER WIRE ONLY. Wire sizes must conform to the

requirements of the National Electrical Code, ANSI/NFPA 70

- latest edition, and all local codes and ordinances. Wire size

and connections must conform with the rating of the appliance.

Copies of the standard listed above may be obtained from:

National Fire Protection Association

Batterymarch Park

Quincy, Massachusetts 02269

This appliance should be connected directly to the fused

disconnect (or circuit breaker) through flexible, armored or

nonmetallic sheathed copper cable. Allow some slack in the

cable so the appliance can be moved if servicing is ever nec-

essary. A UL Listed, 1/2" conduit connector must be provided

at each end of the power supply cable (at the appliance and

at the junction box)

• Venting system MUST terminate outside the

home.

• DO NOT terminate the ductwork in an attic or

other enclosed space.

• DO NOT use 4" laundry-type wall caps.

• Flexible-type ductwork is not recommended.

• DO NOT obstruct the flow of combustion and

ventilation air.

• Failure to follow venting requirements may result

in a fire.

When making the electrical connection, cut a 1 1/4" hole in the

wall. A hole cut through wood must be sanded until smooth. A

hole through metal must have a grommet.
WARNING - TO REDUCE THE RISK OF FIRE OR ELECTRIC

SHOCK, do not use this fan with any solid-state speed

control device.
WARNING - TO REDUCE THE RISK OF FIRE, ELECTRICAL

SHOCK, OR INJURY TO PERSONS, OBSERVE THE FOL-

LOWING: Use this unit only in the manner intended by

the manufacturer. If you have any questions, contact the

manufacturer.
Before servicing or cleaning unit, switch power off at service

panel and lock the service disconnecting means to prevent

power from being switched on accidentally. When the

service disconnecting means cannot be locked, securely

fasten a prominent warning device, such as a tag, to the

service panel.
WARNING - TO REDUCE THE RISK OF SHOCK: This fan

must be installed with an isolating wall control/switch.
CAUTION: For General Ventilating Use Only. Do Not Use To

Exhaust Hazardous or Explosive Materials and Vapors.
WARNING - TO REDUCE THE RISK OF FIRE, ELECTRICAL

SHOCK, OR INJURY TO PERSONS, OBSERVE THE FOL-

LOWING: Installation Work And Electrical Wiring Must

Be Done By Qualified Person(s) In Accordance With All

Applicable Codes And Standards, Including Fire-Rated

Construction.
Sufficient air is needed for proper combustion and exhaust-

ing of gases through the flue (chimney) of fuel burning

equipment to prevent backdrafting. Follow the heating

equipment manufacturer's guideline and safety standards

such as those published by the National Fire Protection

Association (NFPA), and the American Society for Heating,

Refrigeration and Air Conditioning Engineers (ASHRAE),

and the local code authorities.
When cutting or drilling into wall or ceiling, do not damage

electrical wiring and other hidden utilities.
Ducted fans must always be vented to the outdoors.

WARNING

• Electrical ground is required on this rangehood.

• If cold water pipe is interrupted by plastic,

nonmetallic gaskets or other materials, DO NOT

use for grounding.

• DO NOT ground to a gas pipe.

• DO NOT have a fuse in the neutral or grounding

circuit. A fuse in the neutral or grounding circuit

could result in electrical shock.

• Check with a qualified electrician if you are in doubt

as to whether the rangehood is properly grounded.

• DO NOT use this appliance with any solid state fan

speed control device.

• Failure to follow electrical requirements may result

in a fire.

WARNING

For residential use only.

!

!

Advertising