INSTALLATION INSTRUCTION - WATTS TYPE NEMA 4X FS20 FLOW SWITCH

GENERAL APPLICATION: For indoors and outdoors installation of high humidity requiring watertight, dusttight and corrosion resistant enclosures.
TYPICAL CONDITIONS: - Equipment splashing water - Leakage or hose directed water - Wind blown dust and water
- Seepage of water - Severe general condensation - Sleet or icy conditions
IMPORTANT: Electrical installation must be performed by a qualified person and in accordance with all local codes.
LOCATION: Flow switch should be installed in horizontal or vertical section of a pipe or tube where there is a straight run of at least 5 pipe diameters
on each side.
MOUNTING: Flow switch should be installed vertically upright in tees or welded fittings.
ELECTRICAL INSTALLATION: Watertight and dusttight installations require the use of rigid galvanized metal conduit and fittings. Temperature
exceeding 180°F requires electrical wiring insulation rated at 75°C or 167°F. Select required mode of operation and electrical wire in accordance with
appropriate diagram (Fig. 1 or 2). Cover flange screws should be torqued to approximately 30-40 inch pound. Following mechanical and electrical instal-
lation, test flow switch for desired operation.
VERTICAL PIPE INSTALLATIONS: Flow rates for vertical installations are not available. However, the FS20 generally operates satisfactorily when in-
stalled in a vertical pipe with either upward or downward flow provided there is no amount of dirt or sediment in the water. In order to confirm satisfactory
operation, it is advisable to hold the FS20 in position to be installed and manually check for “no flow” switch operation (by hand operation of the paddle).

If a reducing tee is not available and a standard tee

is used, install a face bushing in top opening to

keep waterflow indicator as close to tee as possible.

If a welded fitting is to be used, use only a half

coupling. (Make sure hole in main is 1-5/32" dia.

before welding coupling.)

NOTE: PADDLE LENGTH CONFORMS TO

ASTM TEE STANDARD.

USE TEMPLATE BELOW TO TRIM

PADDLE TO REQUIRED LENGTH “L”.

ACTUAL SIZE TEMPLATE TO TRIM DIMENSION “L”

Always check operation of flow switch to make sure paddle

is free to move in the tee, coupling or pipe before finishing

the installation.

“L” refers to trim length in table.

UNDERWRITER’S LABORATORY LISTED

MAXIMUM PRESSURE 175 PSI

MAXIMUM TEMPERATURE 300ºF

A. FINE SENSITIVITY

1. REMOVE SWITCH COVER.

2. FOR FINER SENSITIVITY, TURN

RANGE ADJUSTING SCREW

CLOCKWISE. LOCATED ON

LEVER NEXT TO MICROSWITCH.

B. COARSE SENSITIVITY

1. REMOVE SWITCH COVER.

2. FOR HIGHER FLOW RATE, TURN

RANGE ADJUSTING SCREW

CLOCKWISE. LOCATED WITH

ADJUSTING SPRING.

3. FOR LOWER FLOW RATE, TURN

COUNTER CLOCKWISE.

ADJUSTMENT

TO ADJUST SETTINGS, FOLLOW

A OR B INSTRUCTIONS. BE

SURE FLOW SWITCH COVER IS

REPLACED BEFORE LEAVING

JOB.

PIPE

SIZE

INSTALLATION USING

ASTM TEE

INSTALLATION USING

WELDED FITTING

PADDLE

TEE SIZE

PADDLE

1”

1” x 1” x 1”

1”A Segment

1-1/4”

1-1/4” x 1-1/4” x 1”

1”A Segment &

Trimmed

2”B Segment

1-5/8”

1-1/2”

1-1/2 x 1-1/2” x 1”

1”A Segment &

Trimmed

2”B Segment

1-3/4”

2”

2” x 2” x 1”

1”A Segment &

2” B Segment

1”A Segment & 2”B Segment

2-1/2”

2-1/2” x 2-1/2” x 1”

1”A & 2”B

Segments &

Trimmed 3”C

Segments

1”A & 2”B Segments &

Trimmed 3”C Segments

2-3/4”

3”

3” x 3” x 1”

1”A, 2”B, & 3”C

Segments

1”A, 2”B, & 3”C Segments

4”

1”A, 2”B, 3”C, and

Trimmed 4”D Segments

4-1/4”

5”

1”A, 2”B, 3”C, and

Trimmed 4”D Segments

5-1/4”

6”

1”A, 2”B, 3”C, 4”D Segments

TRIMMED

DIMENSION

“L”

IMPORTANT:

Mount flow switch in position so that the paddle assembly is at a right angle to the flow. The stamped arrow on bottom plate mounting and label arrow on body must both
point in direction of flow.

1-1/8”

1-

3/

4”

1-5/8”

2-1/8”

2-3/4”

3-1/4”

4-1/4”

5-1/4”

6-1/4”

FLOW

FLOW RATES REQUIRED TO ACTUATE No. FS20 FLOW SWITCH IN HORIZONTAL PIPE

Flow rates in U.S. gallons per minute (GPM). Velocity in feet per second (FPS).

*Equipped with extended paddle trimmed to pipe size

*Flow rates for these sizes are calculated.

PADDLE LENGTH: Included with each flow switch are four paddles. Shortest paddle (A) can be used for 1" pipe size only.

Second shortest paddle (B) can be used as is with paddle (A) for 2" pipe size; but must be trimmed for 1-1/4" and 1-1/2" pipe size.

Third shortest paddle (C) can be used as is with paddle (A) and (B) for 3" pipe size, but must be trimmed for 2-1/2" pipe size.

Longest paddle (D) can be used as is with paddle (A), (B) and (C) for 6" pipe size, but must be trimmed for 4" and 5" pipe size.

(A)

(B)

(C)

(D)

 

¡

 

¢

£¤

¥

¡

 

¢

£¤

¦

¡

 

¢§

¤

¨

¡

 

¢§

¤

Extended
Paddle

Pipe Size in Which

Flow Switch Installed

1”

1-1/4”

1-1/2”

2”

2-1/2”

3”

*4”

*5”

*6”

Factory or

Minimum

Flow Setting

ACTIVATION

FLOW

GPM

5.2

7.9

10.0

13.2

20.9

30.0

39.0

58.0

79.9

FPS

2.01

1.74

1.62

1.29

0.92

1.30

1.0

0.94

0.88

DEACTIVATION

GPM

2.0

3.2

5.3

8.1

9.9

12.0

19.0

29.0

39.6

FPS

0.77

0.71

0.86

0.79

0.44

0.52

0.50

0.47

0.44

Maximum

Flow Setting

ACTIVATION FLOW

GPM

11.5

18.0

18.0

34.1

53.9

52.0

73.5

115.0

166.0

FPS

4.44

3.98

2.91

3.33

2.38

2.26

1.86

1.85

1.84

GPM

8.5

14.6

15.1

29.2

44.4

46.1

64.0

92.0

123.0

FPS

3.28

3.23

2.44

2.85

1.96

2.00

1.67

1.48

1.37

DEACTIVATION

Extended

Paddle

IS-FS20

EDP# 5003207 rev 3

COARSE

SENSITITY

ADJUSTMENT

FINE

SENSITITY

ADJUSTMENT

OPTIONS:

“L” Pilot Light

“BSP” British Threaded Body

REPAIRS AND REPLACEMENT

PADDLES AND COVER MAY BE REPLACED IN THE FIELD. OTHER FIELD REPAIRS MUST NOT BE MADE. REPLACEMENT FLOW SWITCHES MAY BE

OBTAINED FROM THE NEAREST WATTS DISTRIBUTOR OR WHOLESALER. WHEN ORDERING A REPLACEMENT SWITCH, SPECIFY PRODUCT NUMBER

AS SHOWN ON THE FLOW SWITCH.

!!

"

#

$

% & '

% & '

(

)

(

(

) * ) +

) +

, !

- " ! " -. /