Rockwell Automation 440R MSR9T Minotaur Safety Relay Manuel d'utilisation

Minotaur msr9t

Advertising
background image

INSTALLATION INSTRUCTIONS / MONTAGEANLEITUNG / NOTICE D'INSTALLATION

MINOTAUR MSR9T

Drawing No. 23879
Issue No. 0

24V AC/DC or 110/230
VAC selectable.
6VA.
1N/O & 1N/C.
2N/O & 1N/C.

250VAC/4A/1000VA Resistive
30VDC/2A/60VA Resistive.
60mS.
500mA T (Replacable).
Red = Power On
Green = Output Relays Closed.
-10

°

C to +55

°

C.

35mm Din Rail.
Housing IP40, Terminals IP20.
16 Way, D=120mm, H=73mm,
W=45mm.
EN 60204 - 1, EN 1088.

Power Supply:

Power Consumption:

Safety Inputs:

Safety Outputs:

Max. Switch,

Voltage/Current/Load:

Drop Out Time:

Internal Fuse:

L.E.D Indication:

Ambient Temperature:

Mounting:

Enclosure Protection:

Housing:

Standard Conformity:

EN 60204-1, EN 1088.
16 Anschlüsse, T = 120mm,
H = 73mm, B = 45mm.
Schnellbefestigung auf
DIN-Normschiene.
Gehäuse IP 40, Anschlüsse IP 20.
Rot = Betriebsspannung
Grün = Ausgangsrelais.
24 VAC/DC oder 110/230
VAC (umschaltbar).
<2 VA.
1 Ö und 1 S.
Relais 2 S + 1 Ö.
4 A /250 VAC / 1000 VA ohmsch
2 A /30 VDC / 60 W ohmsch.
60 ms.
-10

°

C bis +55

°

C.

Entspricht den Normen:

Gehäuse:

Montage:

Schutzart:

LED-Anzeige:

Betriebsspannung:

Leistungsverbrauch:

Eingänge:

Freigabeausgänge:

Schaltleistung:

Sicherung:

Abfallzeit:

Umgebungstemperatur:

24V AC/DC ou 110/230 VAC
Sélection VAC.
6 VA.
1 N/O & 1 N/C.
2 N/O & 1 N/C.

250 VAC / 4A /1000 VA Résistant.
30 VDC / 2A / 60 VA Résistant.
60 ms.
500 MA T (Remplaçable).
Rouge = ON
Vert = Relais de sortie connectés.
de - 10

°

C à 55

°

C.

Rail Din 35mm.
Boltier: IP 40
Terminaux: IP 20.
16 voies, D = 120mm, H = 73mm
W = 45mm.
EN 60204-1, EN 292.

Alimentation:

Consommation:

Canal de sécurité:

Sortie de sécurité:

Pouvoir de coupure,

Tension/Courant/Charge:

Temps de scrutation:

Fusible interne:

Indication par LED:

Température d'amblance:

Montage:

Etanchéite et résistance:

Boltier:

Conformité aux normes:

Technical Specifications

Technische Daten

Specifications Techniques

13

R1

R1

R2

R2

R2

R1

23

31

14

24

32

A1

2

=

A2

S13

+

_

S21

S14

Protection

Circuit

S22

X1

Test

X2

R2

R1

Monitoring Circuit

73

120.0

45.5

K2

K2

K2 K2 K2

K1

K1

K1 K1 K1

MINOTAUR

MSR9T

X1

23

S13

A1

A2

31 32 14 24 X2

S14 S21 S22 13

POWER
SUPPLY

To gain access to switches & fuse flip
off lid with a small screwdriver.

Access to
replaceable
fuse

Voltage
Switch

230V
110V

Isolate power
before opening.

Contactor Monitoring Circuit (+ reset if required)

Switch

Safety Circuit 2

Safety Circuit 1

Aux. Circuit

Supply

Control

Unit

Emergency
stop
switches

Alternative connection

C

C

NOTE: Electromechanical switches require at

minimum 1 N/O & 1N/C contacts for connection

to the MSR9T.

Installation using the
Minotaur MSR9T in
conjunction with
emergency stop and
electromechanical
gate/guard interlock
switch.

(Shown with guard closed
and machine able to
be started)

R

Advertising