XAL127 Loop Expander Card Installation Sheet

EN FR


EN: Installation Sheet

Operation

The XAL127 loop expander card provides an additional device
loop on the control panel. The card expands the control panel's
device capability to 254 device addresses total, 127 per loop
(any combination of detectors and modules).

Installation

The loop expander card connects to connector J7 on the main
circuit board.

Note:

Installation limits are under the jurisdiction of local

authority.

To install the loop expander card:

1. Power down the panel and disconnect the batteries.

2. Locate connector J7 on the main circuit board. It is below

the primary loop card.

3. Connect the card to connector J7 as shown in the

installation diagram. Make sure you properly align the
connector pins and plastic mounting standoffs so that they
lock into place.

4. Connect the field wiring. See “Wiring.”

5. Power up the panel and connect the batteries.

Figure 1: XAL127 installation

Loop expander
card

Connector J7

Plastic mounting
standoffs

Primary loop card

Wiring

The card provides either Class B or Class A wiring options.

Figure 2: Class B wiring

Loop SEC

Loop card

+

Loop PRI

+

Loop

device

Loop

device

Data line