Installation Instructions for THERMO-AIR and THERMO-ZONE units.

Please read instructions carefully before starting.

Mechanical Installation.

1- The air direction may be either vertical or horizontal, but when the unit is installed horizontally, the
cut-out cover must be on top.

2- Do not install elbows closer
than 12 inches to either the

inlet or outlet of the unit.

3- The electronic controller shuts down the heater when there is no air fl ow.
The minimum amount of air required (in cubic feet per minute) to operate the unit is given in the CFM
column of the table (30 CFM per kilowatt).
If CFM is lower than specifi ed, the airfl ow sensor will limit the total capacity according to the airfl ow
available.

4- Attach the unit to a
suitable support.
The 6” model is small enough
to be located between
standard 16” spaced fl oor
joists.
Always allow a minimum
1/2” clearance above the heater.

LTD.

Top

Thermal cut-out

Cover

O.K

.

O.K

.

O.K

.

12''

O.K.

12''

Control

Box

Heater

Wall

Control

Box

Heater

Mur

2'' x 10''

Joist

8''

16''

11 1/2''

1/2''

Clearance

Floor

April 2007. V2.0